Chiller

Availability :
In Stock Customizing , standard in stock
Description: Air cooled and water cooled chiller both are applied for factory and workshop cooling.
Skype : (86) 189 30700197
WhatsApp : (86) 189 3070 0197

 Air cooled type chiller

Air-cooled low-temperature chiller are widely used in plastics, electroplating, painting, electronics, fine chemicals, medicine, food, grain and oil production, solar photovoltaic industry, air separation, automotive environmental test and inspection cabin, engine air intake system, air-conditioning, refrigeration, cold storage, and other industries.

Water cooled type chiller

The use of fully imported copper pipes and automatic elbow welding greatly enhances oxygen tightness and prevents refrigerant leakage. The water cooled type chiller is especially suitable for use in areas where water resources are scarce or water quality is high. It is equipped with a microcomputer controller (with fault self-display function) and imported refrigeration accessories of international famous brands to ensure long-term reliable operation of the unit.

 

Water cooled type chiller

Model WCT-03 WCT-05 WCT-06 WCT-08(D) WCT-10(D) WCT-12(D) WCT-15(D) WCT-20(D) WCT-25(D) WCT-30(D) WCT-40(D) WCT-50(D)
Standard cooling capacity kcal/h
50HZ/60HZ
7405
8858
12358
14792
14672 19040
22848
24777
29732
28569
34283
38081
45700
49553
59464
57620
69144
81528
97834
100792
120916
122636
147232
17606
KW
50HZ/60HZ
8.61
10.3
14.37
17.2
17.06 22.14
26.57
28.81
34.57
33.22
39.86
44.28
53.14
57.62
69.14
67
80.4
94.8
113.76
117.2
140.6
142.6
171.2
20.47
Total input power KW 3.05 5.18 5.75 7.96 10.36 11.5 15 19.5 20.06 28.62 36.38 43.78
Power 3PH 380V  50HZ(200V/220V/415V   50HZ/60HZ)
Cooling Agent Name R407C
Control mode Capillary pipe (capillary) external balance thermal expansion valve
Compressor Type Fully enclosed scroll type (piston type)
Power (KW) 2.68 4.63 5.2 3.43*2 4.63*2 5.2*2 6.75*2 9*2 9.93*2 12.31*2 16.69*2 20.39*2
Condenser Type Shell and tube type
Cooling water flow(m3/h) 1.77 2.96 3.52 4.57 5.95 6.85 9.14 11.89 13.71 20.5 26.7 33
2.1 3.55 4.22 5.48 7.13 8.22 10.96 14.27 16.45 22.7 29.7 36.6
Inlet and outlet pipe diameter 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 1 1/2″ 2″ 2″ 2 1/2″ 3″ 3″ 3″
Evaporator Type Water tank coil (shell and tube type)
Chilled water flow(m3/h) 1.48 2.47 2.9 3.8 4.95 5.71 7.61 9.91 11.53 16.32 20.18 24.55
1.77 2.96 3.52 4.57 5.94 6.85 9.14 11.89 13.84 19.58 24.2 29.5
Tank capacity(L) 60 60 90 150 200 200 330 330 350 450 580 620
Inlet and outlet pipe diameter 1″ 1″ 1″ 1″ 1″ 1-1/2″ 2″ 2″ 2-1/2″ 2-1/2″ 2-1/2″ 3″
Water pump Power(KW) 0.37 0.55 0.55 1.1 1.1 1.1 1.5 1.5 2.2 2.2 3 3
Lift(m) 25 25 25 25 25 25 25 25 28 28 28 28
Safety protection Compressor overheat protection, over-current protection, high and low pressure protection, over temperature protection, flow protection, phase sequence/phase loss protection, exhaust overheat protection
Machine dimension Length(mm) 890 890 890 1170 1170 1170 1650 1650 1880 1880 2000 2000
Width (mm) 500 500 500 710 710 810 810 810 710 910 980 980
Height (mm) 840 840 840 1200 1200 1520 1520 1520 1880 1800 1960 1750
Weight of machine Kg 130 150 165 300 430 500 735 820 900 1150 1200 1500
Remarks:

1. The cooling capacity is based on: the temperature of chilled water inlet and outlet is 12°C/7°C, and the temperature of cooling water inlet and outlet is 30°C/35°C.

2. Working range: chilled water temperature range: 5°C to 35°C; chilled water inlet and outlet temperature difference: 3°C to 8°C. Cooling water temperature range: 18°C to 37°C; temperature difference between cooling water inlet and outlet: 3.5°C to 10°C.

Contact us

If possible, kindly suggest please your working industry/process, working pressure, working medium, etc. Given detailed request helps to gain better-matched customized solution. Thanks for your patience.

your request will be responsed within 3 hours, kindly pay attention to your email please.